The optimized zero-request dispatch already violates a connected N-1 thermal limit; candidate-specific firm headroom is not available.
Candidate: load at bus 5 · request 50.0 MW · Q not supplied
Exact baseline cut-set certificates
These exact-rational certificates prove specific zero-request transport cut-set deficits under the recorded outages. They do not certify AC feasibility or candidate hosting capacity.
| Outage | Rated cut element(s) | Proven deficit | Separate exact replay |
|---|---|---|---|
| row 1 | row 4: 3–4 | 54.0 MW | VERIFIED |
| row 2 | row 1: 1–2 | 53.4 MW | VERIFIED |
| row 4 | row 1: 1–2 | 51.0 MW | VERIFIED |
Conditional connection actions
| Outage | Maximum candidate MW | Required curtailment | Binding element |
|---|---|---|---|
| Unavailable: Unavailable · baseline violation. | |||
Smallest modeled rating-relief set
| Element | Total +MVA | Request-attributable +MVA | Driving outage |
|---|---|---|---|
| Unavailable: Unavailable · baseline violation. | |||
Better connection points
| Bus | N-1 thermal headroom | Decision |
|---|---|---|
| Ranking is blocked until the zero-request N-1 violation is fixed. | ||
Traceability, scope and assumptions
Analysis ID: bf547f5425c115b3b6ef
Engine: MWClear 0.6.0
Engine source SHA-256: 22051e119f9ccb721d851d8f965d521e28cbe34d0bdef349ccb18a5524e2d1b9
Input SHA-256: cae3290639d989731d32428aacf30c0b918bc91db73bc54791f3aa62d3f76c70
Rating policy: RATE_A is applied to both N-0 and connected N-1 states
Selected monitored/outage rows: 41 / 41
Recorded model omissions: None recorded
Fast DC/PTDF/LODF screen using RATE_A and generator limits. Recorded preventive-dispatch policy: generator-bounds-constrained preventive dispatch minimizing the worst normal and connected N-1 branch utilization, followed by a strictly convex least-squares tie-break anchored to supplied generator PG. Candidate transfers use bounded proportional generator participation. Redispatch remains idealized within PMIN/PMAX: ramp limits, reserves, costs, and area interchange constraints are not modeled. It also excludes dynamics, protection, constructability, cost, schedule, outage probability, and 3 selected islanding outages. The optional AC badge covers only the snapshots explicitly listed in result.json. “+MVA” is a mathematical rating delta, not a construction design or price. Use this to choose where to study next, not as an interconnection approval.